BESS.EGV
Roof-mounted deflagration venting as the most economical solution.

The REMBE® explosion vent BESS.EGV offers optimum protection for your Battery Energy Storage Systems (BESS). BESS.EGV is available in a range of geometries with customisable burst pressures.
Application
BESS.EGV is suitable for use in a wide range of BESS applications where roof installation is preferred. The standard burst pressure is 0.1 bar at 22 °C (71.6°F), but can be modified to suit any BESS design, as low as 0.025 bar.
Advantages
- High venting capacity and full bore opening due to low surface weight.
- High stability and opening speed through integrated bionic structure.
- Adapts perfectly to your BESS due to the wide range of EGV geometries available.
- Quick and easy installation as EGV is torque independent. No additional counter frame required.
- Significant space savings due to the integrated gasket and frame in the explosion vent.
Mechanism
When pressure rises during a deflagration, the vent opens at the defined breaking point and releases pressure from the BESS into the surrounding area.
Technical data
Product parameters
Standard burst pressure Pstat | 25-500 mbar |
Max. permitted operating pressure | 50 % of Pstat |
Temperature | – 40 to + 180 °C (– 40 to + 356 °F) |
Material | Stainless steel |
Gasket material | FDA approved silicon gasket |
Tolerance | ± 20 % at standard burst pressure |
Recommended torque for M10 screws | 20 Nm |
Our specialists will be pleased to assist you in finding a solution that matches your specific operating conditions.
Applications + Industries
- Battery Energy Storage Systems (BESS)
Certifications

Meets the requirements of NFPA 68